A Field Perspective on Engineering Commissioning Resources
  • Home
    • What's New
  • Blog
    • Blog Support
  • SketchUp Models
    • SketchUp Resources
    • Bureaucratic Affairs Building HHW System Logic Exercise
    • Bureaucratic Affairs Building Scavenger Hunt
    • Chilled Water Plant System Diagram Exercise
    • The HIjend Hotel >
      • Chilled Water Plant Scoping Exercise
      • Ballroom AHU Scoping Exercise
      • Cooling Tower Scoping Exercise
  • Tools
    • Altitude Correction Factor
    • Economizer Evaluation Checklist
    • Eikon for Educators and WindLGC
    • Effective Duct Length Tool
    • Excel Third Axis Tool
    • Excel Time Value Conversion
    • Insulation Savings Tools
    • Logic Diagram Tool >
      • Logic Diagram Example - Discharge Air
      • Logic Diagram Example - CHW Plant 01
      • Logic Diagram Example - VAV AHU
    • Mixed Air Calculations
    • Monitoring Plan Spreadsheet
    • Pipe Friction Chart
    • Plot Digitizer >
      • Plot Digitizer Pump Curve Example
    • Square Law Spreadsheet
    • System Diagram Resources
    • Thermodynamic Diagrams Spreadsheet
    • Universal Translator Data Analysis Tool
    • y = (m * x) + b Spreadsheet
  • Useful Formulas
    • Affinity Laws
    • Circular Equivalent Duct
    • Effective Duct Length
    • FT Guide Appendix C
    • HVAC Equations and Concepts
    • Hydraulic Diameter
    • Pump Power and Energy
    • "Square Law"
  • What's That Thing?
    • Cooling Towers
    • Pumps
    • Valves
  • Resources
    • Bill Coad's Writings
    • Data Logging Resources
    • EBCx Skills Guidebook
    • Energy Design Resources
    • Fisher Controls Valve Cavitation Bulletin
    • Functional Testing Guide
    • Honeywell Gray Manual
    • MCC Powers Bulletins
    • NBCIP Reports
    • PEC Tool Lending Library
    • PID Resources
    • Pneumatic Control Resources
    • Resource List
    • Scoping Resources
    • TAB Resources
    • Vintage Carrier Design Manual
    • VRF Systems
    • Williams' Wisdom
  • Videos
    • Bureaucratic Affairs HHW Logic Answers
    • Cooling Tower Flow Variation
    • Economizer Stratification
    • Functional Testing
    • Induction Principles
    • Monitoring Plans
    • CW Pump Deadheaded by Tower Lift
    • Ripple Effects
    • Testing a Pump
    • The Garden of Low Entropy
    • Variable Flow Systems
  • Training
    • Materials from Classes and Presentations >
      • ACEEE
      • ASHRAE
      • ASHRAE - Engineers Notebook
      • BCxA and NCBC
      • BEST Institute
      • Case Studies
      • ERDC 2020 RCx Academy
      • ELPNW
      • ICEBO
      • Marriott AEP
      • Magazine Articles
      • NAVFAC
      • Pacific Energy Center Design, Performance and Commissioning Issues Classes
      • Pacific Energy Center EBCx Project Review
      • Pacific Energy Center EBCx Workshop Series >
        • EBCx Workshop Series 12
        • EBCx Workshop Series 13
        • EBCx Workshop Series 14
        • EBCx Workshop Series 15 >
          • Student One On One Discussions
        • EBCx Workshop Series 16
        • EBCx Workshop Series 17
        • EBCx Workshop Series 18
      • Portland General Electric
      • U of W >
        • U of W Archive
    • On Demand Training >
      • Benchmarking UCA and Scoping
      • Loads and Psychrometrics
      • Induction Motor Principles
      • Introduction to Functional Testing
      • Scope of Work Documents
      • System Diagraming
    • Training Opportunities
  • Contact
    • Copyright and Permissions
  • Home
    • What's New
  • Blog
    • Blog Support
  • SketchUp Models
    • SketchUp Resources
    • Bureaucratic Affairs Building HHW System Logic Exercise
    • Bureaucratic Affairs Building Scavenger Hunt
    • Chilled Water Plant System Diagram Exercise
    • The HIjend Hotel >
      • Chilled Water Plant Scoping Exercise
      • Ballroom AHU Scoping Exercise
      • Cooling Tower Scoping Exercise
  • Tools
    • Altitude Correction Factor
    • Economizer Evaluation Checklist
    • Eikon for Educators and WindLGC
    • Effective Duct Length Tool
    • Excel Third Axis Tool
    • Excel Time Value Conversion
    • Insulation Savings Tools
    • Logic Diagram Tool >
      • Logic Diagram Example - Discharge Air
      • Logic Diagram Example - CHW Plant 01
      • Logic Diagram Example - VAV AHU
    • Mixed Air Calculations
    • Monitoring Plan Spreadsheet
    • Pipe Friction Chart
    • Plot Digitizer >
      • Plot Digitizer Pump Curve Example
    • Square Law Spreadsheet
    • System Diagram Resources
    • Thermodynamic Diagrams Spreadsheet
    • Universal Translator Data Analysis Tool
    • y = (m * x) + b Spreadsheet
  • Useful Formulas
    • Affinity Laws
    • Circular Equivalent Duct
    • Effective Duct Length
    • FT Guide Appendix C
    • HVAC Equations and Concepts
    • Hydraulic Diameter
    • Pump Power and Energy
    • "Square Law"
  • What's That Thing?
    • Cooling Towers
    • Pumps
    • Valves
  • Resources
    • Bill Coad's Writings
    • Data Logging Resources
    • EBCx Skills Guidebook
    • Energy Design Resources
    • Fisher Controls Valve Cavitation Bulletin
    • Functional Testing Guide
    • Honeywell Gray Manual
    • MCC Powers Bulletins
    • NBCIP Reports
    • PEC Tool Lending Library
    • PID Resources
    • Pneumatic Control Resources
    • Resource List
    • Scoping Resources
    • TAB Resources
    • Vintage Carrier Design Manual
    • VRF Systems
    • Williams' Wisdom
  • Videos
    • Bureaucratic Affairs HHW Logic Answers
    • Cooling Tower Flow Variation
    • Economizer Stratification
    • Functional Testing
    • Induction Principles
    • Monitoring Plans
    • CW Pump Deadheaded by Tower Lift
    • Ripple Effects
    • Testing a Pump
    • The Garden of Low Entropy
    • Variable Flow Systems
  • Training
    • Materials from Classes and Presentations >
      • ACEEE
      • ASHRAE
      • ASHRAE - Engineers Notebook
      • BCxA and NCBC
      • BEST Institute
      • Case Studies
      • ERDC 2020 RCx Academy
      • ELPNW
      • ICEBO
      • Marriott AEP
      • Magazine Articles
      • NAVFAC
      • Pacific Energy Center Design, Performance and Commissioning Issues Classes
      • Pacific Energy Center EBCx Project Review
      • Pacific Energy Center EBCx Workshop Series >
        • EBCx Workshop Series 12
        • EBCx Workshop Series 13
        • EBCx Workshop Series 14
        • EBCx Workshop Series 15 >
          • Student One On One Discussions
        • EBCx Workshop Series 16
        • EBCx Workshop Series 17
        • EBCx Workshop Series 18
      • Portland General Electric
      • U of W >
        • U of W Archive
    • On Demand Training >
      • Benchmarking UCA and Scoping
      • Loads and Psychrometrics
      • Induction Motor Principles
      • Introduction to Functional Testing
      • Scope of Work Documents
      • System Diagraming
    • Training Opportunities
  • Contact
    • Copyright and Permissions

Pacific Energy Center

The resources from the most recent version of the Design, Performance and Commissioning Issues classes that I teach with the Building Performance Team at the Pacific Energy Center are posted below.   These classes tend to build off of each other.  For instance, the Chilled and Condenser Water Systems class assumes you are familiar with the materials in the Pumps and Pipes class.   So, if you attended a class and we reference materials from a previous class that you did not attend, this is where you can find them, just scroll down until you find the class you are looking for.

Since the classes are always evolving, the materials for a current version of a given class may be different from the materials for a past version of the class.  If you took a class in the past and are looking for the materials specific to it, reach out to me via the contact link.  I keep an archive of all of my past classes and I most likely can retrieve what you are looking for and forward it to you if you know the date that you took the class.

The buttons below can be used to jump to the class of interest.  Alternatively, you can scroll down the page until you find the topic you are looking for.

Design, Performance and Commissioning Issues Classes

Design Review for NCx & Beyond (Current Class)
System Diagram Workshop
CHW Plants Basics/Ongoing Cx
Pneumatic Controls
VAV Systems
Variable Speed Drives
System Diagram Workshop
Steam and Hot Water Systems
Pumps and Pipes
Air Side Economizers
Fans, Ducts and AHUs
Control Systems
Logic Diagram Workshop
Chilled & Condenser Water Systems
Best Life Cycle Cost Filter Operation
HW and Steam Basics/Ongoing Cx
Commissioning Heat Pumps
RCx 101 (EBCx Workshop Prerequisite Class)
 
Picture
These are the materials for the current class on Design Review.   I will be uploading the materials on the morning of the class session (there are two sessions - 2024-12-18 and 2024-12-19).  They should be here by 9:00 AM if not earlier.  I will also load any follow up materials to this location after the class sessions.
SESSION 1 - 2024-12-18
01_-_introduction_v2.pdf
File Size: 61306 kb
File Type: pdf
Download File

supporting_materials.zip
File Size: 887 kb
File Type: zip
Download File

SESSION 2 - 2024-12-19
02_-_case_studies_v2.pdf
File Size: 39724 kb
File Type: pdf
Download File

02 - pump_info.zip
File Size: 3972 kb
File Type: zip
Download File

04_-_psych_chart.pdf
File Size: 57 kb
File Type: pdf
Download File

06_-_filters.zip
File Size: 6095 kb
File Type: zip
Download File

01_-_fire_damper_exercise.zip
File Size: 3559 kb
File Type: zip
Download File

03_-_chw_plant_drawing_set.pdf
File Size: 6943 kb
File Type: pdf
Download File

05_-_legacy_issues_exercise.zip
File Size: 73212 kb
File Type: zip
Download File

FOLLOW UP
2024-12-19_follow_up.zip
File Size: 1394 kb
File Type: zip
Download File

 

Commissioning Heat Pumps​

Picture
These are the materials from the most recent version of the heat pump class, which was delivered in November of 2024
FIRST MODULE
01_-_introduction_v11.pdf
File Size: 33552 kb
File Type: pdf
Download File

03_-_a_closer_look_at_heat_pumps_v10.pdf
File Size: 20455 kb
File Type: pdf
Download File

02_-_how_buildings_use_heat_v10.pdf
File Size: 62355 kb
File Type: pdf
Download File

04_-_heat_pump_system_types_v6.pdf
File Size: 2207 kb
File Type: pdf
Download File

refrigeration_resources.zip
File Size: 157264 kb
File Type: zip
Download File

FOLLOW UP
The link in the slides to Roy Dossat's Principles of Refrigeration is broken and I have not been able to figure out how to fix it.  That's the bad news.  The good news is that it turns out I included the .pdf in the Refrigeration Resources zip file above.
SECOND MODULE
00_-_heat_pump_system_types_v7r1.pdf
File Size: 5216 kb
File Type: pdf
Download File

supporting_materials.zip
File Size: 84915 kb
File Type: zip
Download File

01_-_ventilation_integration_v10.pdf
File Size: 59024 kb
File Type: pdf
Download File

For this module, we have found that the amount of time it takes to present the core material can vary significantly depending on the questions and discussion that happen during class.  There have been instances when it took the entire class time allotment to present the core material. But there have been other times when we had time left over, which allows us time for an additional case study or two.   

The materials below support the case studies.  Typically, if there has been extra time, it has been about enough time for one case study.  You will be given the opportunity to vote on which one appeals to you the most at the beginning of class.  Point being that the content below supports discussions/exercises that are optional, time permitting.   So, you may want to wait to download the information until we vote on which topics are of the most interest.  
01_-__colorado_mau_case_study.zip
File Size: 21930 kb
File Type: zip
Download File

03_-__seattle_hrv_case_study.zip
File Size: 14765 kb
File Type: zip
Download File

02_-_seattle_hru_case_study_.zip
File Size: 104043 kb
File Type: zip
Download File

04_-_ft_leavenworth_kansas_doas_case_study.zip
File Size: 6610 kb
File Type: zip
Download File

THIRD MODULE
heat_pump_cx_new_construction_v11.pdf
File Size: 65645 kb
File Type: pdf
Download File

point_list_blank.xlsx
File Size: 17 kb
File Type: xlsx
Download File

supporting_information.zip
File Size: 2448 kb
File Type: zip
Download File

follow_up_-_class_control_system_discussion.zip
File Size: 1 kb
File Type: zip
Download File

FOURTH MODULE
 In addition to these materials, we will also be referencing some of the materials from previous sessions, in particular the water_source_heat_pump_loop.zip file from the third module, so you may want to have those materials downloaded if you do not already have them saved on your local device.
heat_pump_cx_existing_buildings_v14.pdf
File Size: 66315 kb
File Type: pdf
Download File

ncx_water_source_heat_pump_loop.zip
File Size: 30830 kb
File Type: zip
Download File

ebcx_water_source_heat_pump_loop.zip
File Size: 8375 kb
File Type: zip
Download File

vrf_controls_subset_san.pdf
File Size: 48070 kb
File Type: pdf
Download File

mr-1_sequence_of_events.txt
File Size: 3 kb
File Type: txt
Download File

FIFTH MODULE
 In addition to these materials, we will also be referencing some of the materials from previous sessions, in particular the 01_-_ebcx_water_source_heat_pump_loop.zip file from the fourth module, so you may want to have those materials downloaded if you do not already have them saved on your local device.
the_allready_all_electric_building_v4.pdf
File Size: 76737 kb
File Type: pdf
Download File

2024-11-20_central_plant_system_diagrams.zip
File Size: 8091 kb
File Type: zip
Download File

2024-11-20__fan_powered_terminal_unit_information.zip
File Size: 1101 kb
File Type: zip
Download File

 

System Diagram Workshop​

Picture
This is where I will be uploading the materials for the System Diagram Workshop I will help support for the Pacific Energy Center.   The materials for each session will be fully uploaded by approximately 7:30 - 8:00 AM on the day of the class.
01_-_system_diagrams_-_introduction_v14.pdf
File Size: 14099 kb
File Type: pdf
Download File

02_-_basic_concepts_v11.pdf
File Size: 14907 kb
File Type: pdf
Download File

01_-_lab_ahu_exercise.zip
File Size: 19178 kb
File Type: zip
Download File

04_-_hijend_hotel_chw_system_field_verification_exercise.zip
File Size: 2841 kb
File Type: zip
Download File

03_-_hijend_hotel_evaporator_pump_loop_exercise.pdf
File Size: 933 kb
File Type: pdf
Download File

​DAY TWO
02_simple_hhw_system_diagram_in_the_field_v1.pdf
File Size: 8984 kb
File Type: pdf
Download File

05_complex_ahu_system_diagram_in_the_field_v1.pdf
File Size: 2190 kb
File Type: pdf
Download File

FOLLOW UP
The files below capture the "answer" for the exercise where we traced out the HHW system diagram in the field and also has the node analysis technique applied to the Hijend Hotel chilled water system, illustrating how the order of connection for the as installed system relative to the design intent configuration impacts the way the system operates.   These slide decks capture additional details above and beyond what we discussed in class in an effort to provide additional clarification. 
simple_hhw_system_diagram_in_the_field_-_answer_v1.pdf
File Size: 14103 kb
File Type: pdf
Download File

2023-12-16_-_hijend_hotel_node_analysis.pdf
File Size: 715 kb
File Type: pdf
Download File

 

Hot Water and Steam Systems; Basic Principles, Ongoing Commissioning, Operation and Optimization​

Picture
This is where I will be uploading the materials for the class series I will help support on Commissioning Hot Water and Steam Systems.   The materials for each session will be fully uploaded by approximately 7:30 - 8:00 AM on the day of the class.
​DAY ONE
01_-_intro_and_how_buildings_use_heat_v12.pdf
File Size: 19813 kb
File Type: pdf
Download File

support.zip
File Size: 607 kb
File Type: zip
Download File

02_-_how_heat_is_generated_v5.pdf
File Size: 29093 kb
File Type: pdf
Download File

​DAY TWO
01_-_water_source_heat_pump_loop_v1.pdf
File Size: 6402 kb
File Type: pdf
Download File

typical_equipment.zip
File Size: 30203 kb
File Type: zip
Download File

02_-_measuring_steam_consumption_with_an_alarm_clock_v4.pdf
File Size: 28107 kb
File Type: pdf
Download File

finned_tube_radiation_exercise.zip
File Size: 3796 kb
File Type: zip
Download File

 

Chilled Water Plants;  Basic Principles, Ongoing Commissioning, Operation and Optimization

Picture
CLASS MATERIALS

​This is where I will be uploading the materials for the class I will help support on Tuesday and Wednesday, September 19th and 20th, 2023 for Local 39 on the topic of Chilled Water Plants;  Basic Principles, Ongoing Commissioning, Operation and Optimization.   The materials for each session will be fully uploaded by approximately 7:30 - 8:00 AM on the day of the class.

TUESDAY'S MATERIALS
00_-_introduction_v2.pdf
File Size: 6365 kb
File Type: pdf
Download File

01_-_cooling_equipment_v3.pdf
File Size: 19651 kb
File Type: pdf
Download File

03_-_coils_and_heat_exchangers_v3.pdf
File Size: 2544 kb
File Type: pdf
Download File

02__-_heat_rejection_equipment_v3.pdf
File Size: 21598 kb
File Type: pdf
Download File

WEDNESDAY'S MATERIALS
Here is a revised version of the cooling tower slides along with some other files we may use for interactive exercises, time permitting.
02__-_heat_rejection_equipment_v3r1.pdf
File Size: 22102 kb
File Type: pdf
Download File

design_intent_system_diagram.pptx
File Size: 93 kb
File Type: pptx
Download File

2023-09-19_load_profile_example.xlsx
File Size: 845 kb
File Type: xlsx
Download File

as_installed_system_diagram.pptx
File Size: 92 kb
File Type: pptx
Download File

These are links to some 3D Tours that we will work with, time permitting.
  • https://tinyurl.com/2023-09-20HijendHotelCHW 
  • https://tinyurl.com/2023-09-20CHWPumpConnection
FOLLOWUP INFORMATION
​
​Here are the resources I mentioned I would provide after class.  Let me know if I forgot anything.
 This is a really well-done YouTube animation that illustrates how a scroll compressor works. (The QR code should also take you there.)
Picture
The sound file to the left was captured from a pump that was cavitating.
Pump Cavitating Sound.wav
File Size: 2479 kb
File Type: wav
Download File

This link and the QR code to the right will take you to the paper Steve Taylor wrote about low delta t syndrome.   There is also information on variable flow systems that discusses this on the blog support page of this site.  And the Variable Flow Systems video page of the site provides a number of videos that discuss variable flow plant operation as well as the evolution from constant flow to variable flow operation.
Picture
ADDITIONAL RESOURCES

​​These are resources that folks who attend a class on a topic like this often find helpful.
copeland_refrigeration_manual.zip
File Size: 10504 kb
File Type: zip
Download File

sporlan.zip
File Size: 15972 kb
File Type: zip
Download File

parker_p-h_diagram.pdf
File Size: 272 kb
File Type: pdf
Download File

roy_dossat_principles_of_refrigeration.zip
File Size: 32686 kb
File Type: zip
Download File

national_refrigerants_reference_guide.zip
File Size: 2239 kb
File Type: zip
Download File

refrigerants_supplement_v1.pptx
File Size: 448 kb
File Type: pptx
Download File

 



Design Review for New Construction Commissioning and Beyond

​Day 1 - 2023-04-25

Picture
These are the materials for the first module of the Design Review Class I am helping to support today (April 25, 2023).
2023-04-25_design_review_v1.pdf
File Size: 13240 kb
File Type: pdf
Download File

2023-04-25_fire_damper_exercise.zip
File Size: 3559 kb
File Type: zip
Download File

2023-04-25_pump_curve_exercise.pptx
File Size: 1769 kb
File Type: pptx
Download File

2023-04-25_boiler_submittal_exercise.zip
File Size: 2519 kb
File Type: zip
Download File

2023-04-25_assignment.zip
File Size: 8813 kb
File Type: zip
Download File

​Day 1 - 2023-04-25

2023-04-26_design_review_v3.pdf
File Size: 8884 kb
File Type: pdf
Download File

2023-04-26_point_list_exercise.zip
File Size: 36 kb
File Type: zip
Download File

2023-04-26_legacy_issues_exercise.zip
File Size: 73212 kb
File Type: zip
Download File

FOLLOW UP INFORMATION

The pump_energy_savings.xlsx file is the calculation we did in class to come up with the lost opportunity associated with the approval of a less efficient pump.

​The damper_pressure_drop_energy_savings_v2.xlsx file is the file from class yesterday where we calculated the savings achieved by using airfoil damper blades for a smoke/fire damper vs. the V groove blades and includes the cost benefit calculation I shared this morning.
​
The affinity_laws_with_details.pptx file is the file I  mentioned that might help explain the "use two 50 hp pumps vs. one 100 hp pump question.   But there could be more to the question than is discussed in the file so feel free to reach out to Ryan for additional clarification, either by discussion with him or by him referring you to me.

​The existing_system_diagram.pdf file is a non-corrupt version of the HHW system diagram file that would not open today.

With regard to the slides about open and closed systems and the video where we demonstrate how the lift of a cooling tower deadheads the pump, both are posted on the newly created CW Pump Deadheaded by Tower Lift page of the site.

pump_energy_savings.xlsx
File Size: 293 kb
File Type: xlsx
Download File

affinity_laws_with_details.pptx
File Size: 15089 kb
File Type: pptx
Download File

damper_pressure_drop_energy_savings_v2.xlsx
File Size: 354 kb
File Type: xlsx
Download File

existing_system_diagram.pdf
File Size: 11861 kb
File Type: pdf
Download File

 



RCx 101

Picture
These are the materials for the RCx 101 class I am helping to support today (March 7, 2023).
2023-03-07_rcx_101_v1.pdf
File Size: 26383 kb
File Type: pdf
Download File

2023-03-07_rcx_101_utility_data.zip
File Size: 18 kb
File Type: zip
Download File

 

Air Handling Systems;  Design, Performance, and Commissioning Issues 

Picture
We will be using Poll Everywhere occasionally during the class, so please take a few minutes to set yourself up to access my Poll Everywhere account as described in these slides
coonnecting_to_poll_everywhere_v4_no_fs_v4.pptx
File Size: 1674 kb
File Type: pptx
Download File

The files below is the primary presentation I will be using in the class.
2022-04-12_01_-_introduction_v12.pdf
File Size: 9863 kb
File Type: pdf
Download File

SUPPORTING INFORMATION
​I will be referring to portions of the files below as I move through the class, depending on there questions and where the interative discussions take us.
2022-04-12_supporting_information.zip
File Size: 180348 kb
File Type: zip
Download File

2022-04-12_relationships.zip
File Size: 43 kb
File Type: zip
Download File

EXERCISE MATERIALS
​These materials will support some of the exercises I have planned in addition to the models.
basic_psych_chart_exercise_v1.pptx
File Size: 528 kb
File Type: pptx
Download File

psych_chart_exercise_v1.pptx
File Size: 2060 kb
File Type: pptx
Download File

perfect_economizer_exercise_1_v1.pptx
File Size: 638 kb
File Type: pptx
Download File

SKETCHUP MODELS
For those who are planning to follow along in the SketchUp Models as I navigate through them in class for the interactive exercises, these are the models I will be using.  Note that I have included two versions of each file type;  one that is back-saved to SketchUp Version 8 for those using legacy versions and another saved as SketchUp Version 2021, which allows a smaller file size to be used and will be compatible with SketchUp Viewer 2021 or later.  The files with SUv8 in the name are, as you might expect, the SketchUp Version 8 files.
main_conference_room_v2.skp
File Size: 31296 kb
File Type: skp
Download File

main_conference_room_v1_suv8.skp
File Size: 74199 kb
File Type: skp
Download File

ballroom_ahu_v24r2.skp
File Size: 35608 kb
File Type: skp
Download File

plant_v44r2.skp
File Size: 151899 kb
File Type: skp
Download File

cooling_towers_v11.skp
File Size: 24209 kb
File Type: skp
Download File

ballroom_ahu_v24r2_suv8.skp
File Size: 81234 kb
File Type: skp
Download File

plant_v44r2_pump_test1_suv8.zip
File Size: 123572 kb
File Type: zip
Download File

cooling_towers_v11_suv8.skp
File Size: 48738 kb
File Type: skp
Download File

 

Best Life Cycle Cost Based Filter Operation

Picture
Picture
CLASS MATERIALS

​The materials below are what we will be using in the class today.  I will also place any follow up information here with-in a week of the class date.
2021_filters_pec_v1.pdf
File Size: 31127 kb
File Type: pdf
Download File

filter_loading_model_gen_2_v11_class.xlsx
File Size: 51356 kb
File Type: xlsx
Download File

filter_loading_data.zip
File Size: 8311 kb
File Type: zip
Download File

 

Heating Hot Water and Steam Systems: Design, Performance, and Commissioning Issues
Day 1 - 2021-11-17

PRE-CLASS PREPARATION
In order to maximize the amount of time we have to interactively focus on the class topic, we will be assuming that you are familiar with pump and piping system basics.  There are a number of resources you can review to get up to speed on the subject. 
​
  • Modules 1 - 5 of the RCx University HVAC Fundamentals: Pumping Systems play list.
  • Modules 2 and 3 of the presentation materials provided with the Pumps;  Design, Performance, and Commissioning Issues class will complement the RCxU information if you want a bit more information.
We will be using a model of a building called the Bureaucratic Affairs Building for some of our exercises.   The model has been set up to support EBCx activities and like any EBCx project, developing a general understanding of the facility, its systems, and its history will be useful information in terms of understanding the current issues and opportunities.  Towards that end, please take the time to download and read through the description of the Bureaucratic Affairs Building Description file to the right.  You may need to reference during class in addition to reading through it ahead of time.
bureaucratic_affairs_building_description_v5.pdf
File Size: 533 kb
File Type: pdf
Download File


Be aware that prior to two to weeks ahead of the class, the materials at the links above may not be the recommended class preparation materials for the current class;  they may be the materials for a previous class. The title of the class is the "give-away".
​
SKETCHUP
This class will use SketchUp models some of the interactive exercises.  While it is not absolutely essential that you install and become familiar with SketchUp to take this class, doing so will make the class a richer experience since you will not be constrained to the screen shots or videos provided where needed for the exercises and the navigation that is done by the instructor.  It will also set you up for taking additional classes in this format, which is something we will be doing more and more of at the PEC.

If you are interested in working with Sketchup, please note that THE FREE VERSION OF SKETCHUP WILL NOT WORK because once the trial period ends, it requires that you upload the models into a website and work with them in a web browser based version of SketchUp.   THE MODELS WE WILL USE IN THE CLASS ARE TOO LARGE TO UPLOAD TO THE WEB BROWSER BASED VERSION. (Not yelling at you, just making sure you notice because its important).

There are several work-arounds for this, including installing SketchUp Viewer (the easiest option if you have a 64 bit computer) or installing one of the legacy versions of SketchUp where the free version ran on your local desktop.   You will find the details regarding these options along with instructions and links for downloading and installing the one you select on the SketchUp Resources  page of the website.

If you are going to install SketchUp, you should also review the information regarding the details of installing it, tutorials on the basic navigation skills you will need, and how to use the Scenes feature of SketchUp.

Bottom line, it is not essential or mandatory that you install SketchUp to take the class.   So please to not let a reluctance to install SketchUp and become familiar with navigating in it stop you from taking the class. You will still be able to interact with the models via the instructor’s navigation during the interactive discussions an via screen shots that will be provided as needed to support exercises.

CLASS MATERIALS

The files below are the materials you will need for todays class session.   

You will also want to download a copy of the mixed air calculation spreadsheet tool on this page of the site for one of our breakout sessions.

Finally, we will be using the Building Performance Database tool at one point.  So, if you don't have an account already, you may want to follow the link now and take a minute and set one up prior to the point we will use it in class.

presentation_pdfs.zip
File Size: 106428 kb
File Type: zip
Download File

utiolity_analysis_breakout.pdf
File Size: 2768 kb
File Type: pdf
Download File

measuring_steam_consumption_with_an_alarm_clock_v2.pdf
File Size: 46479 kb
File Type: pdf
Download File

coil_models_for_training.zip
File Size: 5587 kb
File Type: zip
Download File

measuring_steam_exercise_materials.zip
File Size: 454 kb
File Type: zip
Download File

 FOLLOW UP
During class, I mentioned an informal video I had done for a client to explain and document for them how their variable flow primary secondary heating hot water system worked.  It also touches on the system diagram concept and using it to do diagnostics on the system.  So you may find it to be a helpful reference if you are working with that type of system for the first time.  You'll find the video on the Variable Flow HHW System video page of the website.

I also mentioned that I would provide some resources regarding temperatures for domestic hot water systems, in particular with regard to legionella.  One resource, geared more towards health care applications than not is (appropriately enough) legionella.org/.  But I also had an ASHRAE journal article on legionella in residential domestic water systems that includes some recommendations, so I have uploaded that below along with the section from the ASHRAE Guideline on legionella below.  
05-2004_residential_legionella.pdf
File Size: 224 kb
File Type: pdf
Download File

pages_from_ashrae_guideline_12-2000_legionellosis.pdf
File Size: 439 kb
File Type: pdf
Download File

Heating Hot Water and Steam Systems: Design, Performance, and Commissioning Issues
Day 2 - 2021-12-01

PRE-CLASS PREPARATION
The second day of the class will involve several interactive exercises, at least one of which will involve working with a SketchUp model.   So please review the information provided in the Day 1 Pre-class Preparation section above regarding SketchUp if you have not already done that.

We will also be working with calculations involving the properties of steam so if don't have a set of steam tables and charts, you may want to download the water/steam thermodynamic diagram set provided on the Thermodynamic Diagrams Spreadsheet page of the website.  In addition, the series of blog posts titled What is the Energy Content of a Pound of Steam is an informal narrative for  some of the concepts we will explore in the class session.  So you may find them helpful to review prior to the class or to refer to after the class.

CLASS MATERIALS
The following materials will be used to support the class today.  Note that it is not essential that you use the SketchUp model.  we will work with that interactively.  But when I do a session that way, some folks still like to follow along on their own in a copy of the model so I am making it available for those who wish to do that.

Over the course of the session, we will be working with a number of HVAC relationships.   You will find a copy of them along with other useful HVAC information on the HVAC Equations and Concepts page of the website.  We will also work with a spreadsheet tool that you can use to assess the savings to be achieved by insulating valves and fittings in steam and hot water systems that you will find on the Insulation Savings Tools page of the website.

Also note that we will be using some of the materials from the first day, so you will want to be sure you have access to them.

steam_and_hhw_day_2.pptx
File Size: 1263 kb
File Type: pptx
Download File

05_-_humidifiers_v5.pptx
File Size: 4568 kb
File Type: pptx
Download File

bureacracy_building_v13_hw_logic_suv8.skp
File Size: 147926 kb
File Type: skp
Download File

ftr_and_hx_logic_exercise_materials.zip
File Size: 15292 kb
File Type: zip
Download File

ballroom_ahu_v24_suv8.skp
File Size: 64618 kb
File Type: skp
Download File

preheat_energy_exercise.zip
File Size: 6554 kb
File Type: zip
Download File

energy_calculations_exercise.zip
File Size: 19068 kb
File Type: zip
Download File

 

2021 A Field Perspective on Pneumatic Control and Actuation Systems
​Day 3

Picture
Here are the materials we will be using today in class.  I will place any follow-up materials here with-in a week.
proportional_control_vs_vrf.pptx
File Size: 1022 kb
File Type: pptx
Download File

cv_lab_ahu_v1.pdf
File Size: 85 kb
File Type: pdf
Download File

pneumatic_control_diagram_symbols_v8.pptx
File Size: 135330 kb
File Type: pptx
Download File

thermostat_symbol.pptx
File Size: 7737 kb
File Type: pptx
Download File

equipment_information.zip
File Size: 89772 kb
File Type: zip
Download File

drawing_sheet_v1.xlsm
File Size: 157 kb
File Type: xlsm
Download File

2021 A Field Perspective on Pneumatic Control and Actuation Systems
​Day 2

Here are the materials we will be using today in class.  I will place any follow-up materials here with-in a week.
pneumatics_day_2_pdf_presentations.zip
File Size: 24018 kb
File Type: zip
Download File

supporting_information.zip
File Size: 17968 kb
File Type: zip
Download File

2021 A Field Perspective on Pneumatic Control and Actuation Systems
​Day 1

These are the materials I will be using for the first half-day session on Wednesday, June 23, 2021.   I will post the materials for the second half day session scheduled for Wednesday, June 30, 2021 immediately below this by 7:30 AM on the  morning of the class.
​
There may be some Poll Everywhere activities during the class so please take a minute prior to class o to set up your device to access my account if needed.  The slides below describe how to do this.
coonnecting_to_poll_everywhere_v4.pptx
File Size: 1882 kb
File Type: pptx
Download File

pneumatics_day_1_pdf_presentations.zip
File Size: 24681 kb
File Type: zip
Download File

supporting_information_-_catalogs.zip
File Size: 6945 kb
File Type: zip
Download File

supporting_information_-_control_and_logic_diagrams.zip
File Size: 26785 kb
File Type: zip
Download File

pneumatic_actuator_motion_v1.mp4
File Size: 15366 kb
File Type: mp4
Download File

We will be using this video clip in a breakout session. You can also download the .mp 4 file to the left to view the clip on your laptop but it will not have the table of contents feature that is included with the embedded version above.
 

Pumps and Piping:  Design, Performance and Commissioning Issues

Picture
Picture
​

These are the materials I will be using in the April 29th Pumps class that I am helping to support.  I will also post any follow up materials at this location after the class.

As mentioned in the class registration confirmation and preparation e-mail, we will be using the SketchUp models below for some of the exercises in the class.   The information you need regarding how to get set up with SketchUp was included in the e-mail you received along with links to the other preparatory materials.  But you will also find the information regarding getting a copy of SketchUp on the SketchUp Resources page of the website.
 
If  you want to take a tour narrated tour of the plant rather than working directly with the SketchUp models, there is a "fly through" video at this link. 

There is also a longer narrated video of the plant at this link, where I walk you through the it, point out some of the features, and discuss how you might start making a system diagram and develop a retrocommissioning findings list based on the "obvious indicators" of opportunity.
pumps_and_piping_presentation_pdfs.zip
File Size: 37772 kb
File Type: zip
Download File

plant_v41_suv8.zip
File Size: 111155 kb
File Type: zip
Download File

exercise_support.zip
File Size: 8350 kb
File Type: zip
Download File

ballroom_ahu_fly_through_v23_suv8.zip
File Size: 21976 kb
File Type: zip
Download File

cooling_towers_v11_suv8.zip
File Size: 20773 kb
File Type: zip
Download File

FOLLOWUP INFORMATION
These are the follow up items I said I would provide during class. If I have missed something, just let me know or contact Ryan an he will let me know.  
pumps_class_notes.pdf
File Size: 854 kb
File Type: pdf
Download File

variable_flow_plants_v6.pptx
File Size: 11287 kb
File Type: pptx
Download File

variable_flow_chiller_plants_v2.pdf
File Size: 810 kb
File Type: pdf
Download File

 

Logic Diagram Workshop

Picture
Picture
These are materials I will use in the November 13, 2019 Logic Diagram Workshop class I will help support at the Pacific Energy Center.  I will also post follow-up materials here after the class.
logic_diagram_workshop_pdfs.zip
File Size: 19559 kb
File Type: zip
Download File

supporting_materials.zip
File Size: 79393 kb
File Type: zip
Download File

Follow-up Information

The zip file below contains the follow up information I mentioned that I would provide in class.
follow-up.zip
File Size: 22740 kb
File Type: zip
Download File

Also, as I mentioned, I am in the process of making some informal video clips where I walk you through some of the logic examples associated with the HHW system that are included in the answers to the exercise.  
So you may want to check back in a week or two to see if I have them published.  Meanwhile, you will find the answers to the HHW system exercise at this link.  If you want to try a more expanded version of the exercise we did in class, you will find all of the resources on the  Bureaucratic Affairs Building HHW System Logic Exercise page of the website.
 

VSD Class

Picture
Picture
These are the materials for the Variable Speed Drive class that was presented at the Pacific Energy Center on December 12th.  The Follow-up zip file contains additional information that came up in class.  It includes a "READ ME" file that describes the other files.
SketchUp Models (models.zip)
File Size: 86825 kb
File Type: zip
Download File

Scene Guides for SketchUp Models (scene_guides.zip)
File Size: 1506 kb
File Type: zip
Download File

PDF Presentation Files (pdf_presentations.zip)
File Size: 90855 kb
File Type: zip
Download File

Supplemental Information (supplemental_information.zip)
File Size: 108587 kb
File Type: zip
Download File

Follow-up (follow-up.zip)
File Size: 122001 kb
File Type: zip
Download File

 
 

Control Systems;  Design, Performance, and Commissioning Issues

Picture
Picture
These are the materials from the Control Systems class and include the lab guides we use in the hands-on afternoon session.   Even if you did not attended that activity, you might find the lab guides to be useful because they contain a lot of information about the equipment and controllers we used in the lab sessions.  

Note also that the follow up materials folder includes a READ ME file that describes what the other files are.
pdf_presentations.zip
File Size: 70816 kb
File Type: zip
Download File

SketchUp Model (hru1-v5r2_-_kinematics_suversion8.zip)
File Size: 3695 kb
File Type: zip
Download File

Lab Guides (lab_guides.zip)
File Size: 63390 kb
File Type: zip
Download File

Test Examples (sample_cx_tests.zip)
File Size: 265 kb
File Type: zip
Download File

Follow-up Materials (follow-up.zip)
File Size: 31971 kb
File Type: zip
Download File

 

System Diagram Class Materials

Picture
Picture
These are materials I will use for the June 26th System Diagram Workshop that I will help support at the Pacific Energy Center.   I will be uploading materials over the course of the day and early tomorrow morning.  Everything will be up by 7 AM tomorrow, June 26th if not sooner.  So, if you download something before then, be sure to check back to make sure you have everything.
presentation_pdf_files.zip
File Size: 19108 kb
File Type: zip
Download File

plant_v40_suv8.zip
File Size: 75188 kb
File Type: zip
Download File

scene_guides.zip
File Size: 1506 kb
File Type: zip
Download File

cooling_towers_v11_suv8.zip
File Size: 20773 kb
File Type: zip
Download File

ballroom_ahu_v20_suv8.zip
File Size: 13324 kb
File Type: zip
Download File

system_diagram_examples.zip
File Size: 223652 kb
File Type: zip
Download File

mariagarciaalvarez_system_diagram.pptx
File Size: 1668 kb
File Type: pptx
Download File

 
We will be developing some system diagrams in class, so you should consider bringing something to draw with.  A pad of paper and a pencil will do just fine;  graph paper is nice because it helps keep things orderly.  But it's not necessary.   Some of you may be adept at drawing electronically and that works too.  In fact, those who are electronically inclined may want to download a copy of our PowerPoint based System Diagram Tool to work with.

Note that the chilled water plant model (the plant_v40_suv8.zip) is a very large model.   The two files below provide another way to work with the chiller plant model by breaking it up into two, smaller elements;
  1. The central plant itself where the chillers and chilled water pumps are located, and
  2. The utility tunnel with the condenser water pump room at the end of it below the cooling towers
So you may want to download these models too in case your computer runs slowly when using the other model.   There are also some suggestions regarding what to do if your machine is running slow when working with one of the models on the SketchUp Resources page under the topic A Few Details about Installing SketchUp and  Using the Models.
plant_v40_-_no_tunnel_suv8.zip
File Size: 75187 kb
File Type: zip
Download File

tunnel_assembly_v9_suv8.zip
File Size: 18236 kb
File Type: zip
Download File

 

Chilled and Condenser Water Systems;  Design, Performance, and Commissioning Issues

Picture
Picture
This is an all day class that focuses on chilled and condenser water systems and the files are from the most recent version of the class.
SketchUp Models (models.zip)
File Size: 95137 kb
File Type: zip
Download File

System Diagrams (system_diagrams.zip)
File Size: 2788 kb
File Type: zip
Download File

Equations (equations.zip)
File Size: 338 kb
File Type: zip
Download File

Supplemental Slides (supplemnetal_pdf_slides.zip)
File Size: 33863 kb
File Type: zip
Download File

Follow Up Materials (followup_materails.zip)
File Size: 55641 kb
File Type: zip
Download File

 

VAV Systems;  Design Performance and Commissioning Issues

Picture
Picture
This is the space where I will upload the materials for the class Wednesday,  March 7, 2018, on Variable Air Volume Systems.  I have already started that process to get things done while I am traveling.  But there will be some items that I will add later today or early tomorrow morning.  So, if you download something today (March 6, 2018), you should still check back in the morning after 7:00 AM to pick up any additional materials.
I will also post follow-up materials here after the class.
Presentation PDF Files (pdf_files.zip)
File Size: 43781 kb
File Type: zip
Download File

Ballroom AHU Model (ball_room_ahu_v16_low_oa_amca_suv8.skp)
File Size: 34128 kb
File Type: skp
Download File

Exercise Materials (exercise_materials.zip)
File Size: 4111 kb
File Type: zip
Download File

The files below are the followup information from the class.  The reason for two zip files is that one of the follow-up files is large enough that all of them combined together exceeded the size limits for an upload.
One of the follow up items is best provided via a link.  Specifically, several people asked about piping a cooling coil condensate drain.  You will find an explanation of the things you need to consider at this link.  Feel free to get in touch if you still have questions.
Followup Materials 1st File (followup_01.zip)
File Size: 23720 kb
File Type: zip
Download File

Followup Materials 2nd File (followup_02.zip)
File Size: 236950 kb
File Type: zip
Download File

 

Economizers;  Design, Performance and Commissioning Issues

Picture
Picture
These are the materials from the Economizer class.  The class is focused on air side economizers, but the introductory section also discusses water side economizer and points you to some resources associated with them.  Either type has the potential to deliver significant savings by reducing the need for mechanical cooling if they are working properly.  But in many instances, getting them to work properly is a challenge, especially for air side systems.
pdf_presentations.zip
File Size: 42422 kb
File Type: zip
Download File

SketchUp Models (sketchup_models.zip)
File Size: 81949 kb
File Type: zip
Download File

Economizer Analysis Examples (economizer_analysis_examples.zip)
File Size: 90141 kb
File Type: zip
Download File

Economizer Calculation Examples (economizer_calculation_examples.zip)
File Size: 18672 kb
File Type: zip
Download File

Economizer Control (economizer_control.zip)
File Size: 3634 kb
File Type: zip
Download File

The follow up information I mentioned that I would provide in the class is in the zip file below.  Note that it includes a "Read Me" file that describes what each of the files and folders are.